UNIT-1
Syllabus: Static
Relays: Introduction to static relays, merits and demerits.
Solid state relay or static relay
is an electrical relay, in which the response is developed by electrical/ magnetic
/ optical or other components without mechanical movement of components.
In static relay, the
comparison or measurement if electrical quantities is done by a static circuit.
This circuit gives an output signal for the tripping of a circuit breaker.
A static relay or solid
state relay employs semiconductor diodes, transistors, zener diodes, SCRs,
logic gates etc. as its components. In present days, IC’s are used in place of
transistors and as they are more reliable and compact. The simplified block diagram of a
static relay as shown in the figure below;


As said, in static relay the
comparison of the quantities is done by static electronic circuits. Rectifier
converts AC to DC. Under normal conditions, “I” in the relay is zero. During I1
– I2 flows through the relay. This flows to transistor and pulse circuit.
When there is a pulse, the transistor acts as a closed switch and opens the
contacts of circuit breaker.
How
a static relay works
- The output of CTs / PTs / Transducers is rectified in
RECTIFIER.
- The rectified output is fed into the RELAY MEASURING
UNIT.
- The output of measuring unit is then amplified in AMPLIFIER
- The amplified output is given to the OUTPUT DEVICE,
which energizes the trip-coil, when the relay operates.
Advantages and Limitations of Static Relays (SR)
Advantage when
compared with Electro Magnetic Relays
- Static or
Solid State Relays consumes lesser power than the Electromagnetic Relays as static relays have less Burden
on CT’s and PTs, compared to
Electro Magnetic Relays. Static Relays power consumption is one mill watt.
EMR consumes 2 Watts.
- In statics
Relays, there are no moving parts and hence associated problems of arcing
erosion of contacts, replacement of contacts, as in the case of EM relays,
do not exists.
- There is no
gravity effect on the operation of a static relay and hence found suitable
to be used in ships, aircrafts etc, whereas, the EM relays are to be
necessarily used in vertical position and will not work under jerks and
vibrations.
- A single
static relay can perform several functions like over current, under or
over voltage, single
phasing, short-circuit protection, by incorporating the respective
functional blocks. This is not possible in electromagnetic relays.
- Static
relay is very compact, whereas EM relay is not that compact. Highly
superior operating characteristic and accuracy is possible with static
relays, whereas in EM relays, this is not achievable. A speed of 1/2 to 1
cycle of operating time is possible with static relay, which is not
possible with EM relays.
- Use of
static relays in conduction with Transducers, converting even
non-electrical properties like temperature, pressure etc., is possible.
This is not possible in the case of EM relays.
- Static
relays can think’, through its logic circuits’, where as this is not
possible with EM relays’
- Programmable
operations are possible with static relay. i.e., sequential instructions
that direct the microprocessor in the relay to perform the specific
functions.
- Effect of
vibration on static relay is more or less nil. Static relay is not
affected by shocks and hence suitable for earthquake – prone areas, ships,
locomotive etc. EM relays are highly affected by vibrations and shocks.
- Simplified
testing and servicing is possible with static relay. Defective modules can
be replaced quickly. Testing of EM relays is comparatively not simple.
Limitations of Static Relays
1. Electrostatic Discharges
(ESD): Semiconductor components are quite sensitive to
electrostatic discharges developed by rubbing of insulating components. Hence,
during manufacture of static relays, precautions are needed to avoid ESD.
2. Static relays
are sensitive to voltage transients or voltage spikes caused by the
operation of circuit breaker and isolator in the primary circuit of CTs and
PTs. In their secondary circuit, the voltage spike can reach amplitude of 20KV even, but
generally 12KV. In order to avoid this, filter circuit and usage of screen
cables are adopted.
3. Static relays
are temperature dependent. I.e., the characteristics of transistors, diodes
used in a static relay, change with temperature variants. To avoid this, temperature compensation is provided by means of Thermistor circuits.
4. The price of
static is higher than the equivalent electromagnetic
relay. But multifunctional static relays provided economy of cost.
5. Total reliability
of static relays depends upon the various small electronic parts.
Syllabus: Comparators:
amplitude and phase comparators, duality between amplitude and phase
comparators. Introduction to (a) amplitude comparators-circulating current
type, phase splitting type and sampling type, (b) phase comparators-vector
product type and coincidence type.
Comparator is a part of static relay, which receives two or
more inputs to be compared and gives output based on the comparison.
Types of Comparator
The
various types of comparators are;
1. Amplitude Comparator
2. Phase Comparator
3. Hybrid Comparator
Amplitude
Comparator
An amplitude comparator compares the magnitude of two input quantities
irrespective of the angle between them. One of the inputs is the operating
quantity and the other a restraining quantity.
When
the amplitude of the operating quantity exceeds that of restraining quantity,
the relay sends
a tripping signal to the circuit breaker.

-
The Amplitude comparator compares two vector, |A| and |B|
-
Gives an output: the algebraic difference between the magnitudes |A| and |B|
-
Output is +ve, if |A| > |B|
-
Output is –ve, if |A| < |B|
-
Output is zero, if |A| = |B|
Comparison
by ratio:
-
Output is >1, if |A| > |B|
-
Output <1, if |A| < |B|
-
Output is Zero, if |A| is zero.
Amplitude types
of comparator.
1. Integrating comparator
2. Instantaneous comparator
3. Sampling Comparator
Integrating Comparator
- Circulating Current Type
- Opposed Voltage Type
Circulating
Current Type


It
can also be used as impedance relay.
Two rectifier bridges can be
arranged in such a manner as shown in the figure below, to function as
amplitude comparator circulating type.
The
polarized relay operates when S1>S2 where
S1=K1i1 and
S2 = K2i2.
This arrangement gives a sensitive relay whose voltage may be represented in
the VI characteristic of the figure.
Opposed Voltage
type

This type works with voltage input signals derived from PTs. The
operation depends on the difference of the average rectified voltage (V1-V2).Here the
rectifiers are not protected against higher currents. The relay operates when V1
>V2.
Instantaneous
Comparator (Directing Amplitude Comparator) – Averaging Type

Here the restraining signal is rectified and smoothed completely in
order to provide a level restraint.
This is then compared with the peak value of operating signal, which may
or may not be rectified but is smoothened. The tripping signal is provided if
the operating signal exceeds the level of the restraint. The block diagram is
shown in the fig above. Since this method involves smoothening, the operation
is slow. A faster method is phase splitting the wave shapes of instantaneous
amplitude comparator are shown in fig below before rectification and the
averaging circuit can be eliminated.

Phase Comparator
Phase comparison
technique is the most widely
used one for all practical directional, distance, differential and carrier
relays.
If the two input signals are S1 and S2 the output occurs when the inputs have
phase relationship lying within the specified limits.
Both the input must exist for an output to occur. The operation is
independent of their magnitudes and is dependent only on their phase relationship.
The figures below show that the phase comparator is simple form. The function
is defined by the boundary of marginal operation and represented by the
straight lines from the origin of the S-plane.

The condition of operation is β1 < θ < β2.
θ is the angle by which S2 lands
S1. If β1 =
β2 =90o,
the comparator is called cosine
comparator and if β1=0
and β2=180o, it is a sine
comparator.
In short, a phase
comparator compares two input quantities in phase angle (vertically) irrespective of the
magnitude and operates if the phase angle between them is < 90o.
There
are two types of phase
comparators:
1.
Vector
product comparator
2.
Coincidence
type phase comparator.
Vector Product comparator
This comparator
recognizes the vector product or division between the two or more quantities.
Thus, the output is A, B or A/B
Coincidence Comparator
Consider two
signals S1 and S2.
The period of Coincidence of S1 and
S2 will depend on the
phase difference between S1 and
S2. The fig below shows the coincidence of S1 and S2 when S2 lags S1 by less than π/2 ie., θ.
The period of
coincidence of S1 and
S2 with a phase
difference of θ is Ψ = 180o –
θ. Different techniques are used to measure the period of coincidence. Two of
the important types are
2. Coincidence type – Integrating
phase comparator.
Hybrid Comparator
This kind of
comparator compares both magnitude and phase of the input quantities. Hence
this type is of mixed version.
In the hybrid comparator,
both amplitude and phase comparators are used. Inputs are given to a phase
comparator. The output of the phase comparator is given to amplitude
comparator.

Static impedance relays comparing V and I are generally of Hybrid
Comparator.
Level Detector
Level detector determines the level of its input with
reference to a predetermined setting.

When input I exceed the level (L) and the
output (O) of the level detectors exceeds and the output stage of the relays
gets a triggering signal via an amplifier.
Syllabus: Static over Current Relays:
Introduction to instantaneous, definite time, inverse time and directional over
current relays.
Overcurrent Relay Purpose and Ratings
A relay
that operates or picks up when its current exceeds a predetermined value (setting value) is called Overcurrent Relay.
Overcurrent
protection protects electrical power systems against
excessive currents which are caused by short
circuits, ground faults, etc. Overcurrent relays can be used to protect
practically any power system elements, i.e. transmission lines, transformers,
generators, or motors.
For
feeder protection, there would be more than one overcurrent relay to protect
different sections of the feeder. These overcurrent relays need to coordinate
with each other such that the relay nearest fault operates first.
Use
time, current and a combination of both time and current are three ways to
discriminate adjacent overcurrent relays.
Overcurrent Relay gives protection against:
Overcurrent
includes short-circuit protection, and short circuits can be:
1.
Phase faults
2.
Earth faults
3.
Winding faults
Short-circuit
currents are generally several times (5 to 20) full
load current. Hence fast fault clearance is always desirable on
short circuits.
Types of Overcurrent Relay
These are the types of
overcurrent relay:
1.
Instantaneous Overcurrent (Define Current)
Relay
2.
Define Time Overcurrent Relay
3.
Inverse Time Overcurrent Relay (IDMT Relay)
·
Moderately Inverse
·
Very Inverse Time
·
Extremely Inverse
4.
Directional overcurrent Relay
1. Instantaneous Overcurrent relay (Define Current)
Definite current relay operate instantaneously when the current reaches a
predetermined value.

Instantaneous Overcurrent Relay – Definite
Current
·
Operates in a definite time when current exceeds its
Pick-up value.
·
Its operation criterion is only current magnitude (without time delay).
·
Operating time is constant.
·
There is no intentional time delay.
·
Coordination of definite-current relays is based on the
fact that the fault current varies with the position of the fault because of
the difference in the impedance between the fault and the source
·
The relay located furthest from the source operate for a
low current value
·
The operating currents are progressively increased for the
other relays when moving towards the source.
·
It operates in 0.1s or less
Application: This type is applied to the outgoing
feeders.
2. Definite Time Overcurrent Relays
In this type, two conditions must be
satisfied for operation (tripping), current
must exceed the setting value and the fault must be continuous at least a time
equal to time setting of the relay.

Definite time of overcurrent relay
Modern relays may contain more than
one stage of protection each stage includes each own current and time setting.
1.
For Operation of Definite Time Overcurrent Relay operating
time is constant
2.
Its operation is independent of the magnitude of current
above the pick-up value.
3.
It has pick-up and time dial settings, desired time delay
can be set with the help of an intentional time delay mechanism.
4.
Easy to coordinate.
5.
Constant tripping time independent of in feed variation
and fault location.
Drawback
of Relay:
1.
The continuity in the supply cannot be maintained at the
load end in the event of fault.
2.
Time lag is provided which is not desirable in on short
circuits.
3.
It is difficult to co-ordinate and requires changes with
the addition of load.
4.
It is not suitable for long distance transmission lines
where rapid fault clearance is necessary for stability.
5.
Relay have difficulties in distinguishing between Fault
currents at one point or another when fault impedances between these points are
small, thus poor discrimination.
Application:
Definite time overcurrent relay
is used as:
1.
Back up protection of distance relay of transmission line
with time delay.
2.
Back up protection to differential relay of power
transformer with time delay.
3.
Main protection to outgoing feeders and bus couplers with
adjustable time delay setting.
3. Inverse Time Overcurrent Relays (IDMT Relay)
In this type of relays, operating time is inversely changed with current.
So, high current will operate overcurrent relay faster than lower ones. There
are standard inverse, very inverse and extremely inverse types.
Discrimination by both ‘Time’
and ‘Current’. The relay operation time is inversely proportional to the fault
current.
Inverse
Time relays are also referred to as Inverse Definite Minimum Time (IDMT) relay.

Inverse Definite Minimum Time (IDMT)
The operating time of an overcurrent
relay can be moved up (made slower) by adjusting the ‘time dial setting’. The lowest time dial setting (fastest operating time) is generally 0.5 and the
slowest is 10.
·
Operates when current exceeds its pick-up value.
·
Operating time depends on the magnitude of current.
·
It gives inverse time current characteristics at lower
values of fault current and definite time characteristics at higher values
·
An inverse characteristic is obtained if the value of plug
setting multiplier is below 10, for values between 10 and 20 characteristics
tend towards definite time characteristics.
·
Widely used for the protection of distribution lines.
Based on the inverseness it has
three different types:

Inverse types
3.1. Normal Inverse Time Overcurrent Relay
The accuracy of the operating time may range from 5 to
7.5% of the nominal operating time as specified in the relevant norms. The
uncertainty of the operating time and the necessary operating time may require
a grading margin of 0.4 to 0.5 seconds.
It’s used when Fault Current is dependent on generation of fault not fault location.
Normal inverse time Overcurrent Relay is relatively small
change in time per unit of change of current.
Application:
Most frequently used in utility and industrial circuits.
Especially applicable where the fault magnitude is mainly dependent on the
system generating capacity at the time of fault.
3.2. Very Inverse Time Overcurrent Relay
·
Gives more inverse
characteristics than that of IDMT.
·
Used where there is a
reduction in fault current, as the distance from source increases.
·
Particularly effective
with ground faults because of their steep characteristics.
·
Suitable if there is a
substantial reduction of fault current as the fault distance from the power
source increases.
·
Very inverse overcurrent
relays are particularly suitable if the short-circuit current drops rapidly
with the distance from the substation.
·
The grading margin may be
reduced to a value in the range from 0.3 to 0.4 seconds when overcurrent relays
with very inverse characteristics are used.
·
Used when Fault Current
is dependent on fault location.
·
Used when Fault Current
independent of normal changes in generating capacity.
3.3. Extremely Inverse Time Overcurrent Relay
·
It has more inverse
characteristics than that of IDMT and very inverse overcurrent relay.
·
Suitable for the
protection of machines against overheating.
·
The operating time of a
time overcurrent relay with an extremely inverse time-current characteristic is
approximately inversely proportional to the square of the current
·
The use of extremely
inverse overcurrent relays makes it possible to use a short time delay in spite
of high switching-in currents.
·
Used when Fault current
is dependent on fault location
·
Used when Fault current
independent of normal changes in generating capacity.
Application:
·
Suitable for protection of distribution feeders with peak
currents on switching in (refrigerators, pumps, water heaters and so on).
·
Particular suitable for grading and coordinates with fuses
and re closes
·
For the protection of alternators, transformers. Expensive
cables, etc.
3.4. Long Time Inverse Overcurrent
Relay
The main application of long time overcurrent relays is as backup earth
fault protection.
4. Directional
Overcurrent Relays
When the power system is not radial (source on one side of
the line), an overcurrent relay may not be able to provide adequate protection.
This type of relay operates in on direction of current flow and blocks in the
opposite direction.
Three conditions must be satisfied for its operation:
current magnitude, time delay and directionality. The directionality of current
flow can be identified using voltage as a reference of direction.
Application of Overcurrent Relay
Motor Protection:
·
Used against overloads and short-circuits in
stator windings of motor.
·
Inverse time and instantaneous overcurrent
phase and ground
·
Overcurrent relays used for motors above
1000 kW.
Transformer Protection:
·
Used only when the cost of overcurrent
relays are not justified.
·
Extensively also at power-transformer
locations for external-fault back-up protection.
Line Protection:
·
On some sub transmission lines where the
cost of distance relaying cannot be justified.
·
primary ground-fault protection on most
transmission lines where distance relays are used for phase faults.
·
For ground back-up protection on most lines
having pilot relaying for primary protection.
Distribution Protection:
Overcurrent
relaying is very well suited to distribution system protection for the
following reasons:
·
It is basically simple and inexpensive.
·
Very often the relays do not need to be
directional and hence no PT supply is required.
·
It is possible to use a set of two O/C
relays for protection against inter-phase faults and a separate Overcurrent
relay for ground faults.